Bryant 589A User Manual

Page 20

Advertising
background image

Table 4B — Electrical Data — Unit 589A

UNIT

SIZE

589A

V-PH-Hz

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR-FAN

MOTOR

INDOOR-FAN

MOTOR

POWER SUPPLY

AWG 60 C

MIN WIRE

SIZE

MAX WIRE

LENGTH (ft)

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

024

208/230-1-60

187

253

12.9

62.5

1.4

2.0

19.5

30

12

75

030

208/230-1-60

187

253

15.0

76.0

1.4

2.6

22.8

30

10

100

036

208/230-1-60

187

253

16.7

95.0

1.4

2.8

25.1

30

10

95

208/230-3-60

187

253

10.9

75.0

1.4

2.8

17.8

25

12

70

460-3-60

414

506

5.4

40.0

0.8

1.4

9.0

10

14

100

042

208/230-1-60

187

253

20.0

104.0

1.4

3.1

29.5

45

10

80

208/230-3-60

187

253

13.9

88.0

1.4

3.1

21.9

30

10

60

460-3-60

414

506

6.8

44.0

0.8

1.6

10.9

15

14

100

048

208/230-1-60

187

253

26.4

129.0

1.4

7.2

41.6

60

6

100

208/230-3-60

187

253

15.0

99.0

1.4

7.2

27.4

40

10

70

460-3-60

414

506

8.2

49.5

0.8

2.3

13.4

20

14

100

060

208/230-1-60

187

253

32.1

169.0

2.1

7.2

49.4

60

6

100

208/230-3-60

187

253

19.3

123.0

2.1

7.2

33.4

50

8

90

LEGEND

AWG

American Wire Gage

FLA

Full Load Amps

HACR — Heating, Air Conditioning and

Refrigeration

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
RLA

Rated Load Amps

*Fuse or HACR Breaker.

† Carrier Scroll Compressor.
**Copeland Scroll Compressor.

NOTES:
1. In compliance with NEC (National Electrical Code) requirements for

multimotor

and

combination

load

equipment

(refer

to

NEC

Articles 430 and 440), the overcurrent protective device for the unit
shall be fuse or HACR breaker. The CGA (Canadian Gas Associa-
tion) units may be fuse or circuit breaker.

2. Minimum wire size is based on 60 C copper wire. If other than

60 C wire is used, or if length exceeds wire length in table, deter-
mine size from NEC.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is
greater than 2%. Use the following formula to determine the percent-
age of voltage imbalance.

% Voltage imbalance

max voltage deviation from average voltage

= 100 x

average voltage

Example: Supply voltage is 460-3-60.

AB = 452 v
BC = 464 v
AC = 455 v

452

ϩ

464

ϩ

455

Average Voltage =

3

1371

=

3

= 457

Determine maximum deviation from average voltage.
(AB) 457 − 452 = 5 v
(BC) 464 − 457 = 7 v
(AC) 457 − 455 = 2 v
Maximum deviation is 7 v.

Determine percent of voltage imbalance.

7

% Voltage Imbalance = 100 x

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maxi-
mum allowable 2%.

IMPORTANT:

If the supply voltage phase imbalance is more than 2%,

contact your local electric utility company immediately.

—20—

Advertising