Bryant 589A User Manual
Page 6

REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Compressor access
. . . . . . . . . . . . . . . . . . . . . 36 (914)
(Except for NEC requirements)
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Maximum extension of overhangs . . . . . . . . . . . . . . . 48 (1219)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . . 2 (51)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 14 (356)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 0
Flue panel
. . . . . . . . . . . . . . . . . . . . . . . . . 36 (914)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side . . . . . . . . . . . . . . . . 42 (1067)
Unit and ungrounded surfaces, control box side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side . . . . . . . . . . . . . . . . . . 42 (1067)
UNIT
589A
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
CORNER WEIGHT
(lb/kg)
lb
kg
A
B
C
D
024040
208/230-1-60
333
151
104/47
50/23
130/59
49/22
024060
208/230-1-60
345
157
107/49
53/24
133/60
52/24
030040
208/230-1-60
336
153
97/44
66/30
118/54
55/25
030060/080
208/230-1-60
348
158
100/45
69/31
121/55
58/26
036060/080
208/230-1-60, 208/230-3-60, 460-3-60
366
166
94/43
84/38
117/53
71/32
036100/120
208/230-1-60, 208/230-3-60, 460-3-60
378
172
97/44
87/40
120/55
74/34
UNIT
589A
CENTER OF GRAVITY (in./mm)
X
Y
Z
024040
26.71/678
20.06/510
12.65/321
024060
26.64/677
20.12/511
12.65/321
030040
27.06/687
21.05/535
12.65/321
030060/080
26.98/685
21.07/535
12.65/321
036060/080
27.14/689
21.10/536
12.65/321
036100/120
27.06/687
21.12/536
12.65/321
LEGEND
CG
— Center of Gravity
COND — Condenser
LV
— Low Voltage
MAT’L
— Material
NEC
— National Electrical Code
REQ’D — Required
NOTES:
1. Clearances must be maintained to prevent recirculation of air from outdoor-
fan discharge.
2. Adequate clearance around air openings into combustion chamber must
be provided.
Fig. 6 — 589A024-036 Without Base Rail, Unit Dimensions
—6—