Technical data

Rated data

Operation with increased power at a 230 V mains

4

54

EDS84ASC552 EN 9.1

4.2.5

Operation with increased power at a 230 V mains

The controller can be operated with increased continuous power (120% P

aN

) on a more

powerful motor. The overload capacity remains constant as if operated with a continuous

power of 100%; the information about the percentage values provided for the overload

phases still refers to rated data of 100%. Typical application cases include drives for units

with quadratic load characteristics such as pumps and fans.

Note!

Operation with increased power is only permitted ...

ƒ

With the rated data provided for the controller.

ƒ

In the stated mains voltage range.

ƒ

At switching frequencies of 2 kHz and 4 kHz.

ƒ

At a max. ambient temperature of 40 °C.

ƒ

With the stated installation types.

ƒ

With the fuses, cable cross-sections, mains chokes and filters required for

this type of operation.

ƒ

After parameterisation acc. to specification (cp. software manual

EDS84AV...)

Basis of the data
Mains

Voltage

Voltage range

Frequency range

U

Lrated

[V]

U

Lrated

[V]

f [Hz]

1/N/PE AC

230

180 - 0 % ... 264 + 0 %

45 - 0 % ... 65 + 0 %

Mains current at I

aN

Apparent output power

Motor power

with external

mains choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LR

[A]

I

LR

[A]

S

aR

[kVA]

P

aR

[kW]

E84AVxxx2512

3.6

4.1

0.8

0.37

E84AVxxx3712

5.0

-

1.0

0.55

E84AVxxx5512

6.0

6.4

1.3

0.75

E84AVxxx7512

8.4

-

1.7

1.1

E84AVxxx1122

11.9

14.4

2.4

1.5

E84AVxxx1522

13.7

-

3.0

2.2

E84AVxxx2222

-

-

-

-