Lenze · I/O system 1000 · commissioning guidelines for the PLC Designer · DMS 1.2 EN · 11/2012 · TD05
33
4
Mapping the real station structure in the »PLC Designer«
4.4
Configuring I/O modules on the CANopen bus coupler module
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Configuring counter 0
17. Double-click the "EPM_S601_Counter_2xDC24V" device in the device view to open its
settings.
18. Select the "Direction (pulse on A and direction on B") entry for the counter 0 on the Modules
tab in the "Signal evaluation" table line:
Commissioning termination
19. Establish a connection to the control.
20. Load and start application.
21. Enter "4" as the new value in "Counter Control Word" and transmit it via the key
combination <Ctrl>+<F7> to start the counting process.
• As soon as the value has been transmitted and a countable signal is applied to the
respective input, the counter starts counting upwards.
• The value is transmitted cyclically to the control via the CAN bus.