Accuracy*: ± 1% FS
Overpressure: 300%
Burst Pressure: 500%
Supply Voltage: 12–40 VDC

12–35 VAC (VDC output units only)
Supply Current: VDC Units – 10 mA max.

mA Units – 20 mA max.
Enclosure: 18 Ga C. R. Steel NEMA 4 (IP-65)
Finish: Baked on enamel – PMS2GR88B
EMC Conformance: EN 55022, 55024, 61000-3-3,

61000-4-2, 3, 4, 5, 6 & 11
Compensated Temp Range: 0°F to 180°F

(-18°C to 82°C)

T. C. Error: ±0.025%/°F (.03%/°C)
Media Compatibility: Liquid/gases compatible to

316L stainless steel
Port Connection: 1/8" NPT
Environmental: 10–90%RH Non-Condensing
Termination: Unpluggable screw terminal block
Wire Size: 12 Ga max.
Load Impedance: 3K ohms max. at 40 VDC (mA

output units)

1K ohms min. (VDC output units)
Weight: Enclosure 1.0 lbs. (.45 kg)

*Includes non-linearity, hysteresis and non-repeatability

RANGE

OUTPUT

SPECIFICATIONS

Inspection

Requirements

Mounting

R1 (psig)

R2 (psig)

R3 (psig)

R4 (kPa)

0 to 100 / 0 to 50 / 0 to 25

0 to 300 / 0 to 150 / 0 to 75

0 to 500 / 0 to 250 / 0 to 125

0 to 700 / 0 to 350 / 0 to 175

(4–20 mA 2-wire)

(0–5 VDC/0–10 VDC

field selectable)

mA

VDC

For Additional Information See PR-264 Data Sheet

INSTALLATION

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

Model PR-264

Technical Information

TI.264-07

PRESSURE SENSOR

Inspect the package for damage. If damaged, notify the

appropriate carrier immediately. If undamaged, open the

package and inspect the device for obvious damage.

Return damaged products.

Warning:
• Do not use on oxygen service, in an explosive/hazardous

environment, or with flammable/combustible media.

• Disconnect power supply before installation to prevent

electrical shock and equipment damage.

• Make all connections in accordance with the job wiring diagram

and in accordance with national and local electrical codes. Use

copper conductors only.

Caution:
• Use electrostatic discharge precautions (e.g., use of wrist

straps) during installation and wiring to prevent equipment

damage.

• Avoid locations where severe shock or vibration, excessive

moisture or corrosive fumes are present. NEMA Type 4

housings are intended for outdoor use primarily to provide

a degree of protection against wind-blown dust, rain, and

hose-directed water.

• Do not exceed ratings of the device.

• Tools (not provided)

- Digital Volt-ohm Meter (DVM)

- Appropriate screwdriver for mounting screws

- Appropriate drill and drill bit for mounting screws

• Appropriate accessories

• Two #8 self-tapping mounting screws (not provided)

• Training: Installer must be a qualified, experienced technician

Wiring

Use maximum 12 AWG wire for wiring terminals. Use copper or

stainless steel tubing for the connection to the transducer. Refer

to

Figures 1, 2, 3, & 4 for wiring information and Figures 5 & 6 for

switch designations.

(Wiring Instructions continued on pages 2 and 3.)

ORDERING INFORMATION: PR-264-

R5 (kPa)

R6 (kPa)

0 to 2000 / 0 to 1000 / 0 to 500

0 to 3500 / 0 to 1750 / 0 to 875

RoHS

The PR-264 must be mounted on a vertical surface with the 1/8"

NPT connection pointed downward. Refer to

Figure 7 for

mounting dimensions.
1. Remove the transducer cover using a Phillips head

screwdriver.

2. Select the mounting location.
3. Mount transducer on a vertical surface with two #8 self-tapping

screws (not provided).

4. Pull wires through bottom of enclosure and make necessary

connections.

5. Replace the unit cover and make pneumatic connections.