MAMAC Systems TE-705 User Manual

Rohs, Model te-705, Technical information

Advertising
background image

SPECIFICATIONS

Platinum RTD Sensors:

±0.1% @ 32°F (0°C), Alpha: 385 per DIN 43760

Nickel RTD Sensors (#2):

±0.5°C @ 0°C (32°F), 5,000 PPM/K T.C.R.

Nickel RTD Sensors (#4):

±0.5°F @ 70°F (21.1°C), 6,000 PPM/K T.C.R.

Balco RTD Sensors:

±0.5°F @ 70°F (21.1°C), 4,300 PPM/K T.C.R.

Thermistor Sensors:

±0.2°C interchangeability @ 77°F (25°C)

Operating Temperature:

-40°F to 210°F (-40°C to 100°C)

Probe Material:

3/8" (9 mm) Bendable aluminum

Flange Material:

Galvanized Steel

Steel NEMA-1 (IP-30):

18 Ga. Galvanized Steel

Steel NEMA-4 (IP-65):

18 Ga. Cold Rolled Steel, Powder coated

Warranty:

Five Years (Lifetime on Moisture Migration)

EMC Conformance:

EN 55022, 55024, 61000-3-3,

61000-4-2, 3, 4, 5, 6 & 11

U.S. PATENT NO. 6592254, 7465087

For Additional Information See TE-705 Data Sheet

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

Model TE-705

Technical Information

TI.705-03

DUCT AVERAGING TEMPERATURE SENSORS

RoHS

ORDERING INFORMATION: TE-705-

INSTALLATION

TEMP SENSOR

PROBE

LENGTH

B Galvanized Steel

Enclosure

(NEMA-1 / IP-30)

C Painted Steel

Enclosure

(NEMA-4 / IP-65)

A 6 ft (1.8 m)

B 12 ft (3.6 m)

C 24 ft (7.2 m)

1 100-Ohm Platinum RTD
2 1,000-Ohm Nickel RTD

(5,000 PPM)

3 1,000-Ohm Platinum RTD

4 1,000-Ohm Nickel RTD

(6,000 PPM)

5 1,000-Ohm Balco RTD

7 10,000-Ohm NTC Thermistor

(Type III)

8 10,000-Ohm NTC Thermistor

(Carel)

10 3,000-Ohm NTC Thermistor
12 10,000-Ohm NTC Thermistor

(Type II)
13 5,000-Ohm NTC Thermistor

14 1,035-Ohm Silicon PTC
15 100,000-Ohm NTC Thermistor
16 10,000 ohm NTC Thermistor

..........

(Eliwell)

17 20,000-Ohm NTC Thermistor
18 2,252-Ohm NTC Thermistor
21 1,800-Ohm NTC Thermistor

Example: TE-705-B-10-B-1: Duct Averaging Temp Sensor, NEMA-1 enclosure,
12 ft. bendable 3/8" aluminum, 3,000 ohm NTC thermistor.

1 Bendable

3/8"

Aluminum

PROBE

TYPE

For Resistance vs. Temperature tables, please refer to TI.700-11.

Inspection

Requirements

INSTALLATION

Inspect the package for damage. If damaged, notify the

appropriate carrier immediately. If undamaged, open the

package and inspect the device for obvious damage.

Return damaged products.

•

Tools (not provided)

- Digital Volt-ohm Meter (DVM)
- Appropriate screwdriver for mounting screws
- Appropriate drill and drill bit for mounting screws

•

Appropriate accessories

•

Two #8 self-tapping mounting screws (not provided)

•

Training: Installer must be a qualified, experienced technician.