Mounting

Location: Install the sensor in a location where it will sample the average

duct air temperature. Avoid areas where the air is stratified because these

areas can cause sensing errors.

TE-705: Refer to Figure 2 for mounting dimensions.

1. Drill a 7/16-inch (11 mm) hole into the duct where the sensor will

be installed.

2. Gently uncoil the sensor’s rigid probe and insert it into the duct.

3. Use the flange as a template to mark and drill two holes for the #8

self-tapping sheet metal screws (not provided).

4. Fasten the sensor to the duct with the sheet metal screws. Refer

to Figure 1.

Figure 1 - Installing the TE-705 Sensor

CHECKOUT

Allow the sensor to stabilize in the duct air stream for a minimum of five minutes

before taking a resistance measurement.

1. Disconnect the sensor lead wires from the controller.
2. Connect an ohmmeter across the lead wires.
3. Ensure that nominal resistance measurements are in accordance

with the resistance/temperature curves. (Refer to Tables 1 & 2.

For complete Resistance vs. Temperature tables, please refer to

TI.700-11 - Temperature Sensor section.)
4. Reconnect sensor lead wires to the controller.
5. Check operation of the complete control system.

MAINTENANCE

Regular maintenance of the total system is recommended to

assure sustained optimum performance.

FIELD REPAIR

None. Replace with a functional unit.

DIMENSIONAL DATA

Figure 2 - TE-705 Duct Averaging Temperature Sensor dimensions shown in

inches and millimeters (mm).

4.00" (102 mm)

2.00"

(51 mm)

1/2"

knockout

2.50"

(64 mm)

1/2" NPT fitting

1/2" knockout

Two #8 self-tapping

screws (not included)

System duct

or plenum

Probe

For Technical / Application Assistance call your nearest office

8189 Century Boulevard • Minneapolis, MN 55317-8002 • USA

800-843-5116 • 952-556-4900 • Fax 952-556-4997

[email protected] • www.mamacsys.com

EUROPE

4200 Waterside Centre

Solihull Parkway

Birmingham • West Midlands

B37 7YN • United Kingdom

01384-271113 • Fax 01384-271114

AUSTRALIA

4 Armiger Court, Unit 2

Adelaide • S.A.

5088 • Australia

08-8395-4333 • Fax 08-8395-4433

CANADA

675 Cochrane Drive

East Tower • 6th Floor

Toronto • Ontario

L3R 0B8 • Canada

905-474-9215 • Fax 905-474-0876

ASIA

1 Fullerton Road #02-01

One Fullerton

Singapore • 049213

65-31581826 • Fax 65-31581826

MAMAC Systems, Inc., reserves the right to change any specifications

without notice to improve performance, reliability, or function of our products.

Advertising