VIII. STEP 8 — ADJUST FACTORY-INSTALLED OPTIONS

A. Disconnect Switch

The optional disconnect switch is non-fused. The switch has
the capability of being locked in place for safety purposes.

B. Perfect Humidity™ Dehumidification System

Perfect Humidity system operation can be controlled by field
installation of a Bryant-approved humidistat device (Fig. 13),
or light commercial Thermidistat™ device (Fig. 14). To install
the humidistat device:

1. Route humidistat cable through hole provided in unit

corner post.

2. Feed wires through the raceway built into the corner

post to the 24-v barrier located on the left side of the
control box. See Fig. 12. The raceway provides the
UL-required clearance between high-voltage and low-
voltage wiring.

3. Use a wire nut to connect humidistat cable into low-

voltage wiring as shown in Fig. 15.

To install Thermidistat device:

1. Route Thermidistat cable through hole provided in

unit corner post.

2. Feed the wires through the raceway built into the cor-

ner post to the 24-v barrier located on the left side of
the control box. See Fig. 12. The raceway provides the
UL-required clearance between high and low voltage
wiring.

3. A field-supplied relay must be installed between the

Thermidistat device and the Perfect Humidity circuit
(recommended relay: HN612KK324). See Fig. 16. The
relay coil is connected between the DEHUM output
and C (common) of the unit. The relay controls the
Perfect Humidity solenoid valve and must be wired
between the Perfect Humidity fuse and the low-pres-
sure switch. Refer to the installation instructions
included with the Bryant Light Commercial Thermi-
distat device for more information.

% RELATIVE HUMIDITY

Fig. 13 — Accessory Field-Installed Humidistat Device

Fig. 14 — Light Commercial Thermidistat Device

Fig. 15 — Typical Perfect Humidity Dehumidification System

Humidistat Wiring (208/230-v Unit Shown)

C

— Contactor (Compressor)

CB

— Circuit Breaker

CR

— Cooling Relay

DHR

— Dehumidify Relay

DSV

— Discharge Solenoid Valve

HU

— Humidistat

LPS

—

Low Pressure Switch

LSV

— Liquid Line Solenoid Valve

LTLO

—

Low Temperature Lockout

TRAN

— Transformer

Terminal (Unmarked)

Splice

Factory Wiring

Accessory or Optional Wiring

LEGEND