Bryant DURAPAC PLUS 581B User Manual

Page 41

Advertising
background image

41

NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the
outdoor motor speed controller jumpered to run the fan at full speed.

Fig. 52 — Cooling Charging Chart, 581B036 with the

Perfect Humidity Dehumidification System

NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the
outdoor motor speed controller jumpered to run the fan at full speed.

Fig. 53 — Cooling Charging Chart, 581B048 with the

Perfect Humidity Dehumidification System

NOTE: When using the charging charts, it is important that only the subcooling/reheat dehu-
midification coil liquid line solenoid valve be energized. The subcooling/reheat dehumidifica-
tion coil liquid line solenoid valve MUST be energized to use the charging charts and the
outdoor motor speed controller jumpered to run the fan at full speed.

Fig. 54 — Cooling Charging Chart, 581B060 with the

Perfect Humidity Dehumidification System

NOTE: When using the charging charts, it is important that only the subcooling/reheat
dehumidification coil liquid line solenoid valve be energized. The subcooling/reheat dehu-
midification coil liquid line solenoid valve MUST be energized to use the charging charts
and the outdoor motor speed controller jumpered to run the fan at full speed.

Fig. 55 — Cooling Charging Chart, 581B072 with the

Perfect Humidity Dehumidification System

CONDENSER FAN MUST BE OPERATING

CONDENSER FAN MUST BE OPERATING

CONDENSER FAN MUST BE OPERATING

CONDENSER FAN MUST BE OPERATING