PAGE 34 — DCA-45SSIU3 (60 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (11/30/05)

6. Preheat the engine

glow plugs by turning the ignition

key (Figure 42) to the “OPERATION” position.

Figure 43. Pre-Heat Indicator Lamp

8. Let the engine run for 3-5 minutes, listen and check for

any abnormal sounds or smells. Check for fuel leaks,
and noises that would associate with a loose cover or
hardware. If any of the above mentioned conditions
exists, shut-down the engine and correct the problem.

7. When the preheat lamp illuminates (Figure 43), turn the

ignition key to the “START” position. Once the engine
starts, release the ignition key and allow it to return to
the “OPERATION” position (Figure 42).

Figure 42. Ignition Switch (Operation

Pre-Heat Position)

DCA-45SSIU3 (60 Hz) — GENERATOR START-UP PROCEDURE

The engine's exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating.
Direct exhaust away from nearby personnel.

Before Starting

Figure 40. Engine Enclosure Doors

1. Place the

main, G.F.C.I., and aux. circuit breakers

(Figure 39) in the OFF position prior to starting the engine.

2. Connect the load to the

receptacles or the Output

Terminal Lugs as shown in Figure 13. These load
connection points can be found on the output terminal
panel and the output terminal panel’s hard wire hookup
panel.

3. The output terminal lugs are protected by a plastic cover.

Remove this cover to gain access to the terminals.
Tighten terminal nuts securely to prevent load wires from
slipping out.

4. Close all engine enclosure doors (Figure 40).

Figure 39. Main, Aux. and GFCI

Circuit Breakers (OFF)

NEVER! manually start the engine with the main, GFCI
or

auxiliary circuit breakers in the ON (closed) position.

5. Place the

voltage selector switch in the desired voltage

position (Figure 41).

Figure 41. Voltage

Selector Switch

CAUTION - LETHAL EXHAUST HAZARD

WARNING - STARTING THE GENERATOR