Multiquip DCA45SSIU3 User Manual

Page 36

Advertising
background image

PAGE 36 — DCA-45SSIU3 (60 HZ) — OPERATION AND PARTS MANUAL — REV. #0 (11/30/05)

NORMAL SHUT-DOWN

To shutdown the generator, use the following procedure:

1. Switch the MAIN, AUX and GFCI circuit breakers

(Figure 53) to the “OFF” position (no load).

Figure 53. Main, AUX. and GFCI

Circuit Breakers (OFF)

EMERGENCY SHUT-DOWN

SHUTDOWN

1. To shut-down the engine in the event of an emergency,

switch the

MAIN, GFCI and LOAD (Figure 55) circuit

breakers to “OFF” position.

2. Turn the ignition switch key to the “STOP” position.

2. Let the engine cool by running it for 3-5 minutes with no

load applied (circuit breakers in the off position).

3. Place the ignition switch (Figure 54) in the “STOP” position,

remove the key and store in a safe place.

Figure 54. Ignition Switch (Stop Position)

4. Remove

all loads from the generator.

Figure 55. Ignition Switch (Off Position)

DCA-45SSIU3 (60 Hz) — GEN. START-UP PROCEDURE/SHUTDOWN

16. Turn the

main, GFCI, and aux. circuit breakers to the

ON” position (Figure 51).

17. Observe the generator's ammeter (Figure 52) and verify

it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if the load is in use.

18. The generator will run until manually stopped or an

abnormal condition occurs.

Figure 52. Ammeter (Load)

Figure 51. Main, AUX. and GFCI

Circuit Breakers (ON)