8.

Install each replacement battery. Line up the locking strip on the back of the battery
with the strip on the inside back of the housing and push the battery firmly onto the
strip. You should feel a “click” when the locking strips engage and lock.

9.

Install the positive and negative connections to the appropriate battery terminals (see
Figure 3 and Figure 4).

10. Turn on power to the controller.

11. Turn on the controller.

12. When the controller has completed its warm-up sequence, install the jumper wire

between the two batteries (see Figure 3 and Figure 4).

13. Close the standby battery housing door.

14. The on/off switch on the Beacon 110 and Beacon 200 controls AC power to the

instruments. Verify that the standby battery is installed properly by flipping the on/
off switch on a Beacon 110 or Beacon 200 to the off position and observing that the
controller continues to operate powered by the standby battery.

15. Flip the controller on/off switch to the on position.

Parts List

Table 3 below lists spare parts for the standby battery.

Table 3: Standby Battery Spare Parts

Part Number

Description

18-0107RK

3/4” NPT conduit hub

18-0112RK

Vent

45-0600RK

Wire nut, for 22 - 14 AWG wire

49-1551RK-01

Battery, lead acid, 12 V, 1.2 amp hour, w/self locking fastener strip

Advertising