RKI Instruments 35-3001-01-03 User Manual

Page 14

Advertising
background image

10 • 35-3001-01-03 Methane Sample-Draw Detector

8.

Connect the wires to the applicable detector/transmitter terminal strip at the controller as
shown in Figure 5. Refer to the controller operator’s manual and the controller detector head
specification sheet for the 35-3001-01-03 for detector/terminal strip connections specific to the
controller.

Figure 5: Wiring the Sample-Draw Detector to a Controller

9.

If shielded cable is used, connect the cable’s drain wire to an available chassis (earth) ground at
the controller. RKI controllers typically have a ground stud that can be used to ground the
cable’s drain wire.

Green

B lack

Red

W hite

Not U sed on

This V ersion

LEL/IR

PATS101PATS101

PATS201PATS201

AMP 2

LEL/IR

OXY

OXY

AMP 1

AMP 1

AMP 2

Red

Green

B lack

W hite

+ 24 V DC

Controller D etector/

Transm itter T erm inal

Strip T erminal s

Controller D etector/

Transm itter T erm inal

Strip, LE L D etector

Term inals

- (DC G round)

To I R CH4

Sensor