Maintenance – RKI Instruments 61-1000RKSS-05 User Manual

Page 11

Advertising
background image

61-1000RKSS-05 Combustible Gas Detector• 7

9.

When zeroing operation is complete, turn the regulator’s on/off knob clockwise to
close it.

10. Unscrew the calibration cup from the detector.

11. Unscrew the regulator from the zero air calibration cylinder. For convenience, leave

the sample tubing connected to the regulator and the calibration cup.

12. Store the components of the calibration kit in a safe and convenient place.

Maintenance

This section describes maintenance procedures. It includes preventive maintenance,
troubleshooting, and component replacement procedures.

Preventive Maintenance

This section describes a preventive maintenance schedule to ensure the optimum
performance of the combustible gas detector. It includes daily, monthly, and quarterly
procedures.

Daily

Verify a display reading of 0% LEL at the controller. Investigate significant changes in the
reading.

Monthly

This procedure describes a test to verify that the combustible gas detector responds
properly to the target gas.

WARNING: The controller is not an active gas monitoring device during the response

test procedure.

NOTE:

Performing a response test on the combustible detector may cause alarms. Be
sure to put the controller into its calibration program or disable external alarms
before performing this test.

NOTE:

The following procedure assumes the use of a calibration kit which includes a
calibration gas cylinder, a 0.5 LPM fixed flow regulator with an on/off knob, a
calibration cup for the detector, and a length of sample tubing.

Preparing for the response test

1.

Place the controller into its calibration program or disable external alarms.

2.

Verify that the controller display reading is 0% LEL.

If the display reading is not 0% LEL, set the zero reading of the detector as described
in the Start Up section of this manual, then continue this procedure.

WARNING: Do not remove the junction box cover while the circuits are energized

unless the area is determined to be non-hazardous. Keep the junction box
cover tightly closed during operation.

3.

Screw the regulator into the calibration cylinder.