Troubleshooting – RKI Instruments 65-2321RK User Manual

Page 14

Advertising
background image

10 • 65-2321RK Oxygen Transmitter

4.

When the display reading rises above the decreasing alarm setpoint, return the
controller to normal operation.

Quarterly

Calibrate the oxygen transmitter as described in “Calibration” on page 13 of this manual.
See the calibration frequency discussion in “Calibration Frequency” on page 13 to
determine if a quarterly calibration schedule fits your needs.

Troubleshooting

The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the oxygen transmitter.

NOTE:

This troubleshooting guide describes transmitter problems only. See the
controller operator’s manual for problems you may encounter with the
controller.

Table 2:Troubleshooting the Oxygen Transmitter

Condition

Symptom(s)

Probable Causes

Recommended Action

Fail Condition

• Controller indicates a

fail condition.

• The transmitter wiring

is disconnected or
misconnected.

• The plug-in sensor is

not properly plugged
into the sockets in the
detector housing body.

• The transmitter’s zero

reading is low enough
to cause a fail
condition.

• The transmitter is

malfunctioning.

1. Verify that the transmitter wiring is

correct and secure.

2. Confirm that the plug-in sensor is

installed properly.

3. Perform a fresh air adjustment. A full

calibration is recommended.

4. If the fail condition continues, replace

the plug-in sensor as described later
in this section.

5. If the fail condition continues, contact

RKI for further instruction.

Slow or No
Response/
Difficult or
Unable to
Calibrate

• Transmitter responds

slowly or does not
respond to response
test.

• Unable to accurately

set the fresh air or
zero reading during
calibration.

• Transmitter requires

frequent calibration.

Note: Under “normal”
circumstances, the
transmitter requires
calibration once every 3
months.

Some applications

may require a more
frequent calibration
schedule.

• The calibration cylinder

is low, out-dated, or
defective.

• The calibration gas is

not an appropriate
concentration.

• The transmitter is

malfunctioning.

1. Verify that the calibration cylinder

contains an adequate supply of a
fresh test sample.

2. Check the sensor face for dirt. Clean

if necessary.

3. Verify that the calibration gas

concentration is appropriate for the
transmitter. Zero emission air (20.9%
oxygen) is normally used for a fresh
air adjustment if the environment is
suspect and 100% nitrogen (0%
oxygen) is normally used for a zero
adjustment.

4. If the calibration/response difficulties

continue, replace the plug-in sensor
as described later in this section.

5. If the calibration/response difficulties

continue, contact RKI for further
instruction.