Installation, Mounting the oxygen transmitter – RKI Instruments 65-2322RK User Manual

Page 9

Advertising
background image

65-2322RK Oxygen Transmitter • 5

from a mounting surface and ensure that there is enough room to install a calibration cup
on the detector during calibration.

Installation

This section describes procedures to mount the oxygen transmitter in the monitoring
environment and wire the transmitter to a controller.

Mounting the Oxygen Transmitter

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site that is at normal breathing level.

Figure 3: Mounting the Oxygen Transmitter

2.

At the monitoring site you select, hang or mount the junction box with the detector
facing down (see Figure 3).

.38

.75

3.10

3.65

3/4 NPT
Female

1 1/2 - 20 Thread

for Calibration Cup

J-Box

Oxygen

Detector

8.25 Max

Rubber
Spacer, 3X