65-2336RKSS CO Transmitter • 13

12. Turn on the controller and place into normal operation.

Replacing the CO Detector

NOTE:

In most cases, it is only necessary to replace the plug-in CO sensor.

1.

Turn off the controller.

2.

Turn off or unplug power to the controller.

3.

Remove the junction box cover.

4.

Remove the detector terminal strip from its socket.

5.

Disconnect the detector leads from the detector terminal strip. Note the position of the
color-coded leads as you remove them.

6.

Unscrew the detector from the junction box conduit hub.

7.

Guide the detector leads of the replacement detector through the bottom conduit hub
of the junction box, then screw the mounting threads of the detector into the conduit
hub. If necessary for environmental conditions, apply thread sealant or teflon tape to
the hub and/or detector threads to seal them.

8.

Connect the detector leads to the appropriate detector terminal strip terminals.
Connect the red wire to the terminal labeled TOXIC+ and the black wire to the
terminal labeled TOXIC-. See Figure 4 for the detector wiring connections to the
amplifier.

9.

Reinstall the detector terminal strip into its socket.

10. Turn on or plug in power to the controller.

11. Turn on the controller and place it into normal operation.

CAUTION:

Allow the replacement detector to warm up for 5 minutes before you continue with
the next step.

12. Calibrate the replacement detector as described in “Calibration” on page 14.

13. Secure the junction box cover to the junction box.

Replacing the Amplifier

1.

Turn off the controller.

2.

Turn off or unplug power to the controller.

3.

Remove the junction box cover.

4.

Unplug the detector terminal strip and controller terminal strip from their sockets.
You may leave the wires connected to the terminal strips.

5.

Unscrew and remove the screw with the flat and lock washers that secures the
amplifier to the junction box. The screw is at the bottom right of the amplifier.

6.

Remove the old amplifier.

7.

Place the new amplifier in the same position as the old amplifier. A foam gasket that
orients the amplifier and keeps it from rotating is installed on the bottom of the
amplifier. Make sure the amplifier is seated flat in the junction box.

8.

Install the new amplifier into the junction box with the screw, lock washer, and flat
washer you removed in Step 5.

9.

Install the detector and controller terminal strips into their sockets on the new