Parts list, Returning to normal operation – RKI Instruments 65-2391RK User Manual

Page 19

Advertising
background image

65-2391RK CO

2

Transmitter • 15

Returning to Normal Operation

1.

Remove the voltmeter leads from the amplifier test points.

2.

Unscrew the calibration cup from the detector.

NOTE:

For convenience, leave the regulator and calibration cup connected by the
sample tubing.

3.

Secure the junction box cover to the junction box.

4.

When the display reading falls below the alarm setpoints, return the controller to
normal operation.

5.

Verify that the controller display reading decreases and stabilizes at a typical
background CO

2

level. The 0-5,000 ppm and 0-5 %volume detectors will display a

reading in a fresh air environment because they have low ranges. The 0-50 %volume
and 0-100 %volume detectors will not display a reading in fresh air because their
ranges are too large.

6.

Store the components of the calibration kit in a safe and convenient place.

Parts List

Table 7 lists replacement parts and accessories for the CO

2

transmitter.

Table 7:Parts List

Part Number

Description

06-1248RK

Sample tubing (3/16 in. x 5/16 in.; specify length when ordering)

18-0405RK-01

Junction box (without cover; pre-drilled for amplifier)

18-0406RK

Junction box cover (cover only)

57-1050RK

Amplifier (specify detector part number when ordering)

61-0191RK-02

Infrared CO

2

detector, 0 - 5,000 ppm

61-0191RK-03

Infrared CO

2

detector, 0 - 5% Volume

61-0191RK-05

Infrared CO

2

detector, 0 - 50% Volume

61-0191RK-10

Infrared CO

2

detector, 0 - 100% Volume

65-2391RK-02

CO

2

transmitter, 0 - 5,000 ppm (includes detector, junction box, and amplifier)

65-2391RK-03

CO

2

transmitter, 0 - 5% Volume (includes detector, junction box, and amplifier)

65-2391RK-05

CO

2

transmitter, 0 - 50% Volume (includes detector, junction box, and amplifier)

65-2391RK-10

CO

2

transmitter, 0 - 100% Volume (includes detector, junction box, and amplifier)

71-0121RK

65-2391RK CO2 Transmitter Operator’s Manual (this document)

81-0070RK-01

Steel calibration cylinder, 2,000 ppm CO

2

, 34-liter

81-0072RK-01

Steel calibration cylinder, 2.5% CO

2

, 34-liter