65-2405RKSS Combustible Gas Transmitter • 1

Overview

This manual describes the 65-2405RKSS combustible gas transmitter. This manual also
describes how to install, start up, configure, maintain, and calibrate the transmitter when
it is used with a gas monitoring controller. A parts list at the end of this manual lists
replacement parts and accessories for the combustible gas transmitter.

Specifications

Table 1 lists specifications for the combustible gas transmitter.

WARNING: When using the 65-2405RKSS, you must follow the instructions and

warnings in this manual to assure proper and safe operation of the
65-2405RKSS and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 65-2405RKSS as described in this
manual.

Table 1:Specifications

Description

Specification

Target Gas

Combustible gas, methane calibration standard

1

Area Classification

Explosionproof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Signal Output

4 to 20 mA

Detection Range

0 to 100% LEL

Accuracy

± 5% of reading or ± 2% LEL (whichever is greater)

Response Time

90% in 45 seconds

1

If calibration to a combustible gas other than methane is required, specify the required

calibration gas at time of order.