Installation, Mounting the combustible gas transmitter – RKI Instruments 65-2405RK-05 User Manual

Page 8

Advertising
background image

4 • 65-2405RK-05 Combustible Gas Transmitter

from a mounting surface and ensure that there is enough room to install a calibration cup
on the detector during calibration.

Installation

This section describes procedures to mount the combustible gas transmitter in the
monitoring environment and wire the transmitter to a controller.

Mounting the Combustible Gas Transmitter

1.

Select a mounting site that is representative of the monitoring environment. Consider
the following when you select the mounting site.

Select a site where the transmitter is not likely to be bumped or disturbed. Make
sure there is sufficient room to perform start-up, maintenance, and calibration
procedures.

Select a site where the target gas is likely to be found first. For lighter gases,
mount the detector near the ceiling; for heavier gases, mount the detector near the
floor.

Figure 2: Mounting the Combustible Gas Transmitter

2.

At the monitoring site you select, hang or mount the junction box with the detector
facing down (see Figure 2).

2.70

.38

J-Box

.75

Rubber
Spacer,
3X

3/4 NPT Female

3.65

LEL Detector

3/4 x 1/2

Reducing Bushing

7.5 MAX