Wiring the Combustible Gas Transmitter to a Controller

WARNING: Always verify that the power to the controller is off before you make

wiring connections.

1.

Turn off the controller.

2.

Turn off or unplug power to the controller.

3.

Remove the junction box cover.

4.

The detector leads are factory wired. Verify that the detector leads are wired to the
amplifier’s detector terminal strip as shown in Figure 3.

5.

To gain access to a plug-in terminal strip for wiring, pull it out of its socket by
grasping the terminal strip and pulling. The detector strip is keyed so that the
controller and detector terminal strips cannot be reversed inadvertently.

WARNING: To maintain the explosion proof classification of the detector/junction box

combination, a conduit seal must be used within 18 inches of the junction
box conduit hub used for wiring to the controller.

6.

Guide a three-conductor, shielded cable or three wires in conduit through the top
conduit hub of the junction box.

7.

Pull out the controller terminal strip, and connect the three wires to the terminal strip
as follows (see Figure 3).

Connect the positive wire to the

PWR/SIG “+”

terminal.

Connect the signal wire to the

PWR/SIG “

S”

terminal.

Connect the negative wire to the

PWR/SIG “-”

terminal.

CAUTION:

If shielded cable is used, leave the cable shield’s drain wire disconnected and
insulated at the transmitter. You will connect the opposite end of the cable’s drain
wire to the controller’s chassis (earth) ground.

8.

Reinstall the controller terminal strip into its socket.

9.

Secure the junction box cover to the junction box.

10. Route the cable or wires leading from the combustible gas transmitter through one of

the conduit hubs at the controller housing.

CAUTION:

Do not route power and transmitter wiring through the same controller conduit hub.
The power cable may disrupt the transmission of the transmitter signal to the
controller.

11. Connect the wires to the applicable detector/transmitter terminal strip at the

controller as shown in Figure 3.