RKI Instruments 65-2422RK-05 User Manual

Page 11

Advertising
background image

65-2422RK-05 H

2

S Transmitter • 7

CAUTION:

If using shielded cable, leave the drain wire insulated and disconnected at the
transmitter. You will connect the opposite end of the cable’s drain wire at the
controller.

8.

Secure the junction box cover to the junction box.

9.

Route the cable or wires leading from the H

2

S transmitter through one of the conduit

hubs at the controller housing.

CAUTION:

Do not route power and transmitter wiring through the same conduit hub. The
power cable may disrupt the transmission of the transmitter signal to the controller.

10. Connect the wires to the to the applicable controller transmitter terminal strip as

shown in Figure 3.

Figure 4: Wiring the H

2

S Transmitter to a Controller

11. If shielded cable is used, connect the cable’s drain wire to an available chassis (earth)

ground at the controller. RKI controllers typically have a ground stud that can be used
to ground the cable’s drain wire.

24 V

4/ 20

TOXIC

SPAN

B ATT

F B

ZERO

H2S Detector,
Factory Wired

Jumper Block

Installed To Toxic

Select Header

Red

Black

Controller or Recording

Device

4 - 20 mA In (FB)

+ 24 VDC

Not Used

Factory Set Pot

Amplifier

G

W

RD

B K

TP

+

+

TP

+

TOXIC

OXY

OXY