Troubleshooting – RKI Instruments 65-2437RK-05 User Manual

Page 13

Advertising
background image

65-2437RK-05 CO Detector • 9

6.

When the controller display reading falls below the alarm setpoints, return the
controller to normal operation.

7.

Store the components of the calibration kit in a safe place.

Quarterly

Calibrate the CO detector as described in the Calibration section of this manual.

Troubleshooting

The troubleshooting guide describes symptoms, probable causes, and recommended
action for problems you may encounter with the CO detector.

NOTE:

This troubleshooting guide describes detector problems only. See the controller
operator’s manual for problems you may encounter with the controller.

Table 2: Troubleshooting the CO Detector

Condition

Symptom(s)

Probable Causes

Recommended Action

Fail Condition

Controller indicates a
fail condition.

• The detector wiring is

disconnected or
misconnected.

• The plug-in sensor is

not properly plugged
into the sockets in the
detector housing body.

• The detector’s zero

reading is low enough
to cause a fail
condition.

• The detector is

malfunctioning.

1. Verify that the detector wiring is

correct and secure.

2. Confirm that the plug-in sensor is

installed properly.

3. Perform a zero adjustment. A full

calibration is recommended.

4. If the fail condition continues, replace

the plug-in sensor as described later
in this section.

5. If the fail condition continues, contact

RKI for further instruction.

Slow or No
Response/
Difficult or
Unable to
Calibrate

• Detector responds

slowly or does not
respond during
response test.

• Unable to accurately

set the zero or
response reading
during calibration.

• Detector requires

frequent calibration.

Note: Under “normal”
circumstances, the
detector requires
calibration once every 3
months.

Some applications

may require a more
frequent calibration
schedule.

• The calibration cylinder

is low, out-dated, or
defective.

• The flame arrestor in

the detector housing
cap is wet or clogged
with dirt or other
particulates.

• The calibration gas is

not an appropriate
concentration.

• The detector is

malfunctioning.

1. Verify that the calibration cylinder

contains an adequate supply of a
fresh test sample.

2. Check the detector housing cap to

determine if the flame arrestor is wet
or dirty. Clean if necessary.

3. Verify that the calibration gas

concentration is appropriate for the
detector. Zero emission air (20.9%
oxygen) is normally used for a zero
adjustment if the environment is
suspect and 50 PPM CO in air is
normally used for a response
adjustment.

4. If the calibration/response difficulties

continue, replace the plug-in sensor
as described later in this section.

5. If the calibration/response difficulties

continue, contact RKI for further
instruction.

Unexplained
Upscale
Readings or
Alarms

• Controller indicates a

CO reading that
cannot be verified.

• CO alarms occur at

the controller that
cannot be explained.

• Charcoal filter is

saturated and no
longer scrubbing out
interfering gases.

1. Replace charcoal filter.
2. If difficulties continue, contact RKI for

further instructions.