65-2481RK Multi Point Detector • 1

Overview

This manual describes the 65-2481RK multi point direct connect detector. This manual
also describes how to install, start up, maintain, and calibrate the detector when it is used
with a gas monitoring controller. A parts list at the end of this manual lists replacement
parts and accessories for the detector.

Specifications

WARNING: Do not use this product in a manner not specified in this instruction

manual.

Table 1 lists specifications for the multi-point detector.

Table 1: Specifications

Target Gas

65-2481RK: LEL/O

2

/H

2

S/CO, methane calibration standard for

LEL
65-2481RK-01: LEL (IR CH

4

)/O

2

/H

2

S/CO, methane calibration

for LEL
65-2481RK-02: LEL (IR HC)/O

2

/H

2

S/CO, propane calibration for

LEL
*Note: Since the 65-2481RK is a direct connect detector, the

calibration is done at the controller.

Area Classification

Explosion proof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Detection Range

LEL: 0 to 100 %LEL (lower explosive limit)
O

2

: 0 to 25 %volume

H

2

S: 0 to 100 ppm (parts per million)

CO: 0 to 300 ppm (parts per million)

Response Time

90% in 30 seconds

Accuracy

Catalytic Combustible Gas:
± 5% of reading or ± 2% LEL (whichever is greater)
IR Combustible Gas:
± 5% of reading or ± 2% of full scale (whichever is greater)
Oxygen:
± 0.5% O

2

Hydrogen Sulfide:
± 5% of reading or ± 2 ppm H

2

S (whichever is greater)

Carbon Monoxide:
± 5% of reading or ± 5 ppm CO (whichever is greater)

Operating Temperature

23°F to 104°F (-5°C to 40°C)