Wiring the multi-point detector to a controller – RKI Instruments 65-2480RK User Manual

Page 21

Advertising
background image

65-2480RK Multi Point Detector • 17

Figure 14: Outline and Mounting Dimensions 65-2480RK-54

2.

At the mounting site you select, use #10 screws to mount the detector to a vertical
surface.

CAUTION:

Mount the multi-point detector with the detectors facing down (see Figures 6-14).

Wiring the Multi-Point Detector to a Controller

WARNING: Always verify that the power source is OFF before you make wiring

connections.

1.

Turn off the controller.

2.

Turn off or unplug power to the controller.

3.

Remove the junction box cover.

3/4 INCH NPT HUBS (4X)

.25

3.11

LEL
DETECTOR

1.10

2.40

3/4" CONDUIT

PLUG

CO

DETECTOR

3.00

.20 DIA X .45 Slot,(2X) ,mounting

1.25

3.00

7.63

3.15

8.24 max.