Overview, Specifications – RKI Instruments 65-2484RK-06 User Manual

Page 5

Advertising
background image

65-2484RK-06 Multi Point Detector • 1

Overview

This manual describes the 65-2484RK-06 multi point direct connect detector. This manual
also describes how to install, start up, maintain, and calibrate the detector when it is used
with a gas monitoring controller. A parts list at the end of this manual lists replacement
parts and accessories for the detector.

Specifications

WARNING: Do not use this product in a manner not specified in this instruction

manual.

Table 1 lists specifications for the multi-point detector.

Table 1: Specifications

Target Gas

LEL/O

2

/H

2

S/SO

2

, methane calibration standard for LEL

*Note: Since the 65-2484RK-06 is a direct connect detector, the

calibration is done at the controller.

Sampling Method

Diffusion

Detection Range

LEL: 0 to 100 %LEL (lower explosive limit)
O

2

: 0 to 25 %volume

H

2

S: 0 to 100 ppm (parts per million)

SO

2

: 0 to 6.00 ppm (parts per million)

Response Time

90% in 30 seconds

Accuracy

Catalytic Combustible Gas:
± 5% of reading or ± 2% LEL (whichever is greater)
Oxygen:
± 0.5% O

2

Hydrogen Sulfide:
± 5% of reading or ± 2 ppm H

2

S (whichever is greater)

Sulphur Dioxide:
± 10% of reading or ± 5% of full scale (whichever is greater)

Operating Temperature

23°F to 104°F (-5°C to 40°C)