2495rk, 2498rk, Wiring the h – RKI Instruments 65-2498RK User Manual

Page 8: S detector to a controller

Advertising
background image

4 • 65-2495RK/65-2498RK H

2

S Detector

NOTE:

If your application does not require a specific mounting site, mount the detector
at approximately breathing level.

Figure 3: Outline & Mounting Dimensions, 65-2495RK & 65-2498RK

2.

At the mounting site you select, hang or mount the junction box with the detector
facing down (see Figure 3).

Wiring the H

2

S Detector to a Controller

WARNING: Always verify that power to the controller is OFF before you make wiring

connections.

1.

Turn off the controller.

2.

Turn off or unplug power to the controller.

3.

If the detector is mounted remotely from a controller using the junction box, proceed
to step 4.

If the detector is mounted directly to a controller, it is normally factory wired. Confirm
that the detector’s black and red wires are connected to the appropriate controller
detector terminals and skip to “Start Up” on page 6. See Figure 4, the controller
operator’s manual, and the controller’s detector head specification sheet for the 65-
2495RK detector for the wiring connections.

4.

Remove the junction box cover.

5.

Guide a two-conductor, shielded cable or two wires in conduit through the unused
conduit hub of the junction box. Use appropriate conduit fittings and construction
technique for the environmental rating of the junction box. The junction box is rated
NEMA 4X.

Rubber
Spacer, 3X

.38

.75

2.70

2

H S
Detector

7.30 .25

3.65

3/4" NPT

+

Ø 1.75

1 1/2-20 Thread for

Calibration Cup

65-2495RK

3/4 NPT
Conduit Hub

65-2498RK

1 1/2-20 Thread for

Calibration Cup

Junction

Box

1.32

.75

6.80 Max