65-2641RK-04 M2A Transmitter Operator’s Manual

2

Specifications

Table 1 lists specifications for the M2A.

WARNING:

When using the M2A, you must follow the instructions and warnings in
this manual to assure proper and safe operation of the M2A and to
minimize the risk of personal injury. Be sure to maintain and periodically
calibrate the M2A as described in this manual.

Table 1: M2A Specifications

Target Gas/Detection Range

Hydrogen:
0 - 100% LEL, 1% LEL increments

Alarm Settings
(Alarm 1/Alarm 2)

10 %LEL/50 %LEL

Construction (housing)

Explosion-proof Junction Box, NEMA 4

Area Classification

Explosion-proof for Class I, Groups B, C, and D

Sampling Method

Diffusion

Input Power

10 - 30 VDC

Controls

• Three push button switches
• Three magnetic switches for non-intrusive calibration

Weight

5.5 lbs.

Signal Output

4 to 20 mA with impedance maximums listed below

-12 VDC input: 500 ohms impedance max
-24 VDC input: 1000 ohms impedance max

RS-485 Modbus

Operating Temperature

-40°C to 50°C

Accuracy

± 5% of reading or ± 2% LEL (whichever is greater)

*

These are the RKI factory settings. You can change the alarm settings in Configuration Mode. See

“Viewing & Changing M2A Parameters” on page 23.