65-2610RK-04 M2 Transmitter Operator’s Manual

20

NOTE:

If the M2 is in both an alarm 1 and alarm 2 condition, both the A1 and A2 LEDs
will be on, the gas reading will alternate with the ALMS 1&2 message, and
both alarm relays will energize.

Responding to an Alarm 2 Condition

1.

Follow your established procedure for a high level combustible gas condition.

2.

After the gas reading falls below the alarm 2 setpoint, press the ENTER button to reset
the alarm circuit. Resetting the alarm circuit turns off the A2 light, resets the LCD, and
de-energizes the alarm 2 relay.

NOTE:

If the ENTER button is pressed while the M2 is in an alarm 2 condition, the A2
LED will flash but all other indications will remain unchanged.

You cannot de-energize the alarm 2 relay until the gas reading falls below the
alarm 2 setpoint.

Fail Condition

Fail Condition Indications

The M2 indicates a fail condition for any of the following:

The detector wiring is disconnected or incorrectly connected.

The display reading is -10% of full scale or lower.

When the M2 senses a fail condition, it alerts you as follows:

The F LED turns on.

The gas reading is replaced by the FAIL message.

The fail relay de-energizes.

NOTE:

The fail alarm has a 30 second delay.

Responding to a Fail Condition

1.

Verify that the detector wiring is correctly and securely connected.

Low Power Alarm

Low Power Alarm Indications

The M2 senses a low power condition when the DC power source is 18.5 volts or less.

WARNING:

While in a low power condition, the M2 is not an active gas monitor.

When the M2 senses a low power condition, it alerts you as follows:

The F LED turns on.

The message LowPower is indicated on the top line of the LCD and the input voltage
is displayed on the bottom line of the LCD.

The fail relay de-energizes.