Overview, Specifications – RKI Instruments GD-K71D4X User Manual
Page 4

1 • Model GD-K71D4X Sample Draw Transmitter
Overview
This supplement describes the differences and additional features of the Model GD-
K71D4X compared to the GD-K71D. It also describes how to install, startup, maintain, and
calibrate the GD-K71D4X.
Specifications
Table 1 lists specifications for the GD-K71D4X.
WARNING: When using the GD-K71D4X, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the
GD-K71D4X and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the GD-K71D4X as described in this
manual.
Table 1: Specifications
Target Gas & Detector Range
Refer to the RKI Instruments Inc. List of Detectable Gases
Enclosure Type
NEMA 4X
Sampling Method
Sample-draw
Input Power
24 VDC
Signal Output
4 to 20 mA
Response Time
90% in 60 seconds
Accuracy
See GD-K71D manual
Flow Rate
Approximately 0.5 liters/minute
Recommended Sample Tubing
1/4” O.D. x 1/8” I.D. Teflon PTFE