9 user selectable options menu – SATEC C192PF8-RPR User Manual

Page 39

Advertising
background image

Chapter 4 Setup Menus

34

To select a display option:

Press to activate the middle window, and then use the up/down arrow

keys to scroll to the desired option.

To change the display option:

Press to activate the lower window.
Use the up/down arrow keys to set the desired option.
Press to store your new setting or press to leave your previous

setting unchanged.

To quit the display setup menu:

From the middle window, press or .

4.9 User Selectable Options Menu

This menu allows you to change options which relate to the instrument features
and functionality. Table 4-10 lists all available options with their code names and
applicable ranges.

To select an option:

Press to activate the middle window, and then use the

up/down arrow keys to scroll to the desired option.

To change the selected option:

Press to activate the lower window.
Use the up/down arrow keys to set the desired value.
Press to store your new setting or to leave the

previous setting unchanged.

To quit the display setup menu:

From the middle window, press or .

Table 4-10 User Selectable Options (

default setting)

Code

Parameter Options

Description

P.cAL

Power calculation
mode

rEAc

*

nAct

Using reactive power
Using non-active power

roLL

Energy roll value

10.E4
10.E5
10.E6
10.E7
10.E8

*

10,000 kWh
100,000 kWh
1,000,000 kWh
10,000,000 kWh
100,000,000 kWh

SELECT

SELECT

OPtS

rEAc

P.cAL

ENTER

ESC

ESC

ENTER

SELECT

CHG

OPtS

ENTER

ENTER

SELECT

SELECT

ESC

ESC

ENTER

ENTER

Advertising