IS THERE VOLTAGE FROM IGNITION
CONTROL TO COMBINATION GAS
VALVE?
→CHECK ELECTRICAL WIRES FROM IGNITION
CONTROL TO COMBINATION GAS VALVE
→CHECK IGNITION CONTROL, REPLACE IF
NECESSARY
NO
IS GAS COMING THROUGH
ORIFICE ON THE HEATER?
YES
→ENSURE ALL GAS VALVES ARE OPEN
NO
YES
DOES THE IGNITION CONTROL
TERMINATE THE SPARKING
PROCESS AFTER 21 SECONDS.
→CHECK SPARK IGNITER FOR CRACKS,
REPLACE SPARK IGNITER IF NECESSARY
→REPLACE WITH NEW IGNITION CONTROL
UNIT IF NECESSARY
STILL HAVING TROUBLE
OPERATING THE HEATER?
→REPEAT THE ABOVE TROUBLE SHOOTING
PROCEDURES
→IF THE PROBLEM PERSISTS, CONTACT YOUR
DISTRIBUTOR.