Bryant DURAPAC 551B User Manual

Page 129

Advertising
background image

129

MODEL NUMBER NOMENCLATURE — 558F180-300

ARI* CAPACITY RATINGS

LEGEND

*Air Conditioning and Refrigeration Institute.

NOTES:

1. Rated in accordance with ARI Standards 360-89 and 270-89.
2. The 558F300 is beyond the scope of the ARI Certification Program.
3. ARI ratings are net values, reflecting the effects of circulating fan heat.
4. Ratings are based on:

Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature
and 95 F db air entering outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.

5. All 558F180-300 units are in compliance with ASHRAE 90.1-1999

Energy Standard for minimum SEER and EER requirements. Refer
to state and local codes or visit the following website:
http://solstice.crest.org/efficiency/bcap to determine if compliance with
this standard pertains to a given geographical area of the United
States.
California, Maryland, Washington, Wyoming, Massachusetts and vari-
ous local and state building codes adopted the ASHRAE 90.1-99 effi-
ciency standard on October 29, 2001.

AIR QUANTITY LIMITS

LOW OUTDOOR TEMPERATURE

OPERATING LIMITS (F)

UNIT
558F

NOMINAL

TONS

STANDARD

CFM

NET COOLING

CAPACITY

(Btuh)

TOTAL

WATTS

EER

SOUND

RATING

(dB)

IPLV

180

15

5300

178,000

16,828

9.7

88

9.9

210

18

5500

204,000

20,582

10.0

88

10.5

240

20

6200

236,000

24,559

9.7

95

10.4

300

25

7200

278,000

28,325

9.8

95

10.5

dB

Sound Levels (decibels)

db

Dry Bulb

EER — Energy Efficiency Ratio
IPLV — Integrated Part-Load Values
wb

Wet Bulb

UNIT 558F

MINIMUM CFM

MAXIMUM CFM

180

4500

7,500

210

5400

9,000

240

6000

10,000

300

7000

11,250

UNITS

TEMPERATURE

All

40

180, 210 with Low Ambient Kit

10

240 and 300 with Low Ambient Kit

25

All with Motormaster® Head Pressure Control

–20

Nominal Tons
180
– 15
210 – 18
240 – 20
300 – 25

558F – Medium Efficiency

Electric Cooling Unit

Fan Drive Position
(Standard Motor)*
B
– Standard Low-Medium

Fan Drive Static Capability

D – Alternate High Fan Drive

Static Capability

Voltage Designation
E
– 460-3-60
P – 208/230-3-60

Electric Heaters
000
– No factory-installed electric heaters

Heat Type
X
– No Heat Installed

(Field-installed electric heaters available)

Factory-Installed
Outdoor Air and Other
Upgrade Options
C
– EconoMi$er
H – Manual Outdoor-Air Damper

Design Series Code
AA
– Original Design Series

5 5 8 F E X 2 1 0 0 0 0 A A A A

NOTE: The example model number 558FEX210000DAACB designates an 18 ton 460-3-60 volt electric cooling rooftop unit with scroll compres-
sors, TXVs, EconoMi$er and the standard low-medium fan drive static capability.

0

T

F

Q

0

04
-0
12

55
8F1

80-

30
0

Advertising
This manual is related to the following products: