SDC 632RF User Manual

Test unit annually

Advertising
background image

P:\INSTALLATION INST\Power Supplies\INST-632RF.vsd Rev B 04-13

POWER SUPPLY

INSTALLATION INSTRUCTIONS

MODEL 632RF

801 Avenida Acaso, Camarillo, Ca. 93012

(805) 494-0622 • Fax: (805) 494-8861

www.sdcsecurity.com • E-mail: [email protected]

MAIN SYSTEM ON-OFF OR

FIRE PANEL CONNECTION

Min. Switch or

Contact Ratings

100mA @ 30VDC

POWER SUPPLY SPECIFICATIONS

Input Voltage: 115 VAC @ 60hz
Input Current: 1.0 amps Max.

Output Voltage: 12/24VDC
Output Voltage Ranges:

12 V Operation: 9.2 – 12.0 VDC
24 V Operation: 21.2 – 24.0 VDC

Output Current: 2.0 amps
Ripple Voltage: 0.05 Volts Max.

Battery Charger Max. Current: 0.25 amps
Maximum recommended battery size: 4ah
(Replace batteries every 3 years)

Suitable Uses:
Electric Lock Power Supply
Access Control Power Supply

TEST UNIT ANNUALLY

BATTERY 1

4ah

POWER

SUPPLY

BOARD

BATTERY 1

4ah

COMPONENT LOCATIONS

STANDARD BOX

CONTROL
MODULE

CONTROL
MODULE

MODEL 632RF

12 Volt Mode Battery

Connections

12VDC

SET

SWITCH

FOR

12VDC

+

C

_

+

_

12VDC

SET

SWITCH

FOR

24VDC

+

C

_

+

_

12VDC

24 Volt Mode Battery

Connections

24V

12V

CHG FLOAT

AC VOLTAGE

INPUT

VOLTAGE SELECT

SWITCHES

BATTERY CHARGER

STATUS

BATTERY INPUT

TERMINALS

MANUAL RESET

+

-

C

+

-

SYSTEM STATUS

YELLOW – SYSTEM OK

RED – ON BATTERY PWR
GREEN – NO DC OUTPUT

VOLTAGE OUTPUT

TERMINALS

NORMAL RESET

+

_

C

Fire Panel

Contact (N/C)

+

_

C

Master ON/OFF

Switch (N/C)

Note: Power limited

cable must maintain a

1/4” or more of spacing

from battery cables or

primary power wires.

7ah batteries require an

Auxiliary battery box

Power
Supply

Battery

+

C

_

HIGH

VOLTAGE

INPUT

POWER LIMITED

CLASS 2 OUTPUT

+

_

Advertising