Press temp limits – Sensaphone 400 User Manual

Page 76

Advertising
background image

74

SENSAPHONE 400 User’s Manual

5 .4 .2 dISablIng alarm reSponSe to

hIgh or low temperature

To disable alarm response to either high or low temperature settings exclu-

sively, enter the following temperature limit when programming the select-

ed zone. (The Model 400 will not respond to temperatures encountered at

maximum settings or beyond.) Begin by following the key sequence shown

in Section 5.4.1, and when prompted to enter the high or low temperature

value:
• Set high temperature to either +150º F or +65º C (high temperature limit)

to prevent the Model 400 from responding to a high temperature alarm.

• Set low temperature to either -20° F or -30° C to prevent the Model 400

from responding to a low temperature alarm.

5 .4 .3 InterrogatIng hIgh and low

temperature lImItS

1. Press WHAT IS.

WHAT

IS

2. Press TEMP LIMITS.

5

TEMP LIMITS

3. Press the number key corresponding to the selected temperature zone.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME