Installation, Venting arrangements for vertical terminations – Regency Bellavista B36XT Medium Gas Fireplace User Manual

Page 31

Advertising
background image

Regency Bellavista™ B36XT Gas Fireplace

31

INSTALLATION

VENTING ARRANGEMENTS FOR VERTICAL TERMINATIONS

RIGID PIPE 4" X 6-5/8"

(MUST USE REDUCER PART # 946-606 & 770-994 RIGID PIPE ADAPTOR)

The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 90

o

elbows, with Rigid Pipe

Venting Systems for Propane and Natural Gas. Two 45

o

elbows equal to one 90

o

elbow. Maximum of four 45

o

elbows allowed.

• Vent must be supported at offsets.
• Firestops are required at each fl oor level and whenever passing through a wall.
• Maintain clearances to combustibles as listed in the "Clearances" section.
•

Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting
to 2-14" opening ,1-5/8"opening and to 1-1/16" opening.

Note: Must use optional fl ue adapter when using Rigid Pipe (Part # 770-994).

Maximum:

35.5

ft.

(10.

m)

8

Minimum

8’

(2.4m)

Min.

49”

(1.2m)

Maximum:

25

ft.

(7.6m)

0

2

4

6

40

8

10

12

14

16

18

20

22

24

26

28

30

V

ertical

Height

(Feet)

32

34

36

38

6

8

Horizontal (Feet)

2

0

4

10

12

Restrictor 1-1/16” Open

No Restrictor

Maximum 10’ Centerline to Centerline

Restrictor 1-5/8” Open

Maximum 8’ Centerline to Centerline

Restrictor 2-1/4” Open

Set 2

Set 3

Set 1