Bryant 548F User Manual

Page 27

Advertising
background image

27

Table 16 — Fan Performance, 548F060 High-Static Motor — Vertical Discharge Units

LEGEND

*Motor drive range: 1300 to 1685 rpm. All other rpms require field-

supplied drive.

NOTES:

1. Boldface indicates field-supplied drive is required.

2.

indicates field-supplied motor and drive are required.

3. Values include losses for filters, unit casings, and wet coils. See

Table 7 for accessory/FIOP static pressure information.

4. Maximum continuous bhp is 2.9 and the maximum continuous

watts are 2562. Extensive motor and electrical testing on these
units ensures that the full range of the motor can be utilized with
confidence. Using your fan motors up to the wattage ratings shown
will not result in nuisance tripping or premature motor failure. Unit
warranty will not be affected. See Evaporator-Fan Motor Perfor-
mance, Table 6 for additional information.

5. Use of a field-supplied motor may affect wire sizing. Contact your

Bryant representative for details.

6. Interpolation is permissible. Do not extrapolate.

548F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)*

Airflow

(Cfm)

External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

808

0.42

429

914

0.56

572

1001

0.69

705

1084

0.85

869

1168

1.01

1032

1600

846

0.49

501

950

0.64

645

1034

0.78

797

1111

0.94

961

1194

1.11

1134

1700

884

0.57

582

983

0.72

736

1068

0.88

899

1145

1.03

1053

1218

1.21

1237

1800

924

0.66

674

1018

0.82

838

1105

0.98

1001

1179

1.13

1155

1246

1.32

1349

1900

965

0.76

777

1057

0.92

940

1143

1.10

1124

1212

1.26

1288

1280

1.43

1461

2000

1008

0.87

889

1096

1.04

1063

1177

1.22

1247

1247

1.40

1431

1300

1.57

1604

2100

1051

0.99

1012

1136

1.17

1196

1210

1.35

1380

1284

1.54

1574

1347

1.72

1758

2200

1095

1.12

1145

1173

1.30

1328

1245

1.49

1523

1322

1.70

1737

1380

1.89

1931

2300

1140

1.26

1288

1210

1.47

1502

1284

1.65

1686

1356

1.80

1901

1418

2.07

2115

2400

1185

1.41

1441

1249

1.61

1645

1323

1.80

1860

1389

2.03

2074

1456

2.26

2310

2500

1231

1.57

1604

1289

1.78

1819

1363

2.00

2044

1424

2.22

2269

1500

2.45

2504

548F060 (5 TONS) — HIGH-STATIC MOTOR (BELT DRIVE)* (cont)

Airflow

(Cfm)

External Static Pressure (in. wg)

1.2

1.4

1.6

1.8

2.0

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

Rpm

Bhp

Watts

1500

1199

1.19

1216

1126

1.46

1492

1250

1.69

1757

1301

1.91

1944

1349

2.12

2164

1600

1263

1.28

1308

1275

1.49

1523

1299

1.78

1800

1352

2.01

2047

1401

2.23

2280

1700

1295

1.39

1420

1351

1.58

1615

1352

1.80

1850

1407

2.03

2070

1459

2.26

2305

1800

1319

1.52

1553

1389

1.71

1747

1435

1.91

1952

1494

2.15

2197

1548

2.40

2446

1900

1343

1.64

1676

1415

1.80

1891

1478

2.05

2095

1538

2.31

2358

1594

2.57

2625

2000

1374

1.77

1809

1438

1.99

2034

1505

2.21

2258

1566

2.49

2542

1624

2.77

2830

2100

1409

1.91

1952

1465

2.14

2167

1533

2.45

2501

1596

2.77

2821

1654

3.08

3141

2200

1442

2.08

2126

1498

2.30

2350

1568

2.64

2688

1632

2.97

3031

1691

3.31

3375

2300

1475

2.26

2310

1554

2.64

2698

1627

3.03

3091

1693

3.42

3486

1755

3.81

3881

2400

1565

2.47

2524

1649

2.89

2948

1726

3.31

3379

2500

1596

2.95

3010

1682

3.45

3522

1760

3.96

4036

Bhp

Brake Horsepower Input to Fan

FIOP

Factory-Installed Option

Watts — Input Watts to Motor

Advertising