Bryant 548F User Manual

Page 48

Advertising
background image

Copyright 2000 Bryant Heating & Cooling Systems

CL-1

CATALOG NO. 5354-808

CUT A

L

O

N

G

DO

T

T

E

D

LINE

C

U

T

A

L

ONG DO

T

T

E

D

L

INE

START-UP CHECKLIST

(Remove and Store in Job File)

I. PRELIMINARY

INFORMATION

MODEL NO.: _______________________________________

SERIAL NO.: ________________________________________

DATE:______________________________________________

TECHNICIAN:_______________________________________

JOB LOCATION:____________________________________

II. PRE-START-UP (insert checkmark in box as each item is completed)



VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS



CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS



CHECK THAT INDOOR AIR FILTER IS CLEAN AND IN PLACE



VERIFY THAT UNIT INSTALLATION IS LEVEL



CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS



CHECK PULLEY ALIGNMENT AND BELT TENSION REFER INSTALLATION INSTRUCTIONS
(Size 072 Standard Motor and Sizes 036-060 Alternate Motor and Drives)



ENSURE BELT TENSION IS CORRECT AND BLOWER PULLEYS ARE PROPERLY ALIGNED

III. START-UP:

ELECTRICAL

TEMPERATURES AND PRESSURES

(COOLING MODE)



VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION



VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGE 41 (COOLING MODE) ONLY).
UNIT MUST OPERATE A MINIMUM OF 15 MINUTES BEFORE ADJUSTING CHARGE.

SUPPLY VOLTAGE

L1-L2

L2-L3

L3-L1

COMPRESSOR AMPS

L1

L2

L3

INDOOR-FAN AMPS

L1

L2

L3

OUTDOOR-AIR TEMPERATURE

DB

RETURN-AIR TEMPERATURE

DB

WB

COOLING SUPPLY AIR

DB

WB

REFRIGERANT SUCTION

PSIG

SUCTION LINE TEMPERATURE

F

REFRIGERANT DISCHARGE

PSIG

LIQUID LINE TEMPERATURE

F

Advertising