Setting the configuration, Lcd-8 configuration, Hold-on time – WarmlyYours SCV-DUAL User Manual

Page 12: Temperature set-point, Low temperature lock-out

Advertising
background image

Snow Switch

®

Model LCD–8 Aerial Snow Controller, 100 – 240 VAC

24782 Rev. A 03/13

(800) 234-4239

http://www.networketi.com

11 of 14

Environmental Technology, Inc.

Setting the configuration

There are three fields available for configuration. Each has several numerical

values possible, as follows:

Field 1: Hold-On Time

Values

1: off

2: 1 hour

3: 3 hours*

4: 5 hours

Field 2: Operating Temperature

Values

1: none (precipitation sensor)

2: 36°F / 2.2°C

3: 38°F / 3.3°C*

4: 40°F / 4.4°C

Field 3: Low Temperature Lockout

Values

1: disabled*

2: enabled

*default value

2 second pause

4 second pause; to top

2 second pause

3 hour hold-on

38°F / 3.3°C

Low temperature
lockout disabled

Figure 7. LED response, default configuration

LCD-8 Configuration

The user is able to configure three operating parameters on the Snow Switch

Model LCD–8.

These are:

• the hold-on time in hours;

• the temperature set point in degrees Fahrenheit; and

• low temperature lock-out operation.

The definitions of each of these parameters, as well as how to determine their

current setting and how to change those settings, will be explained in this section of

the manual.

HOLD-ON TIME

Hold-on time refers to the number of hours that the heaters will continue to

operate once the unit no longer detects precipitation. Hold-on time ensures that

not only is all the snow melted from the protected surface, but also that the system

continues to dry and evaporate the surface without refreezing. The factory default

hold-on time setting is 3 hours.

TEMPERATURE SET-POINT

The temperature set-point refers to the temperature at which the LCD-8

activates the heaters given the presence of moisture. When set to its default, “Off,”

the controller activates the heaters based only on the presence of moisture at any

temperature. The factory default temperature set point is 38°F (3.33°C).

LOW TEMPERATURE LOCK-OUT

The low temperature lock-out function disables unit operation in tempera-

tures less than 17°F (–8.33°C) in those climates or during those seasons where it

is simply too cold to make operation practical. The factory default low temperature

lock-out setting is Off, meaning that the unit will try to activate the heaters regard-

less of ambient temperature.