Input range selector 9 10, Current voltage – Weidmuller G168 Ultra SlimPak User Manual

Page 2

Advertising
background image

Description

Diagnostic LEDs

Output

Operation

Dynamic Deadband

The Ultra SlimPak G168 is a DIN rail mount, AC voltage or current input limit alarm with dual setpoints and

two contact closure outputs. The field configurable input and alarm functions offer flexible setpoint capability.

Input voltage spans from 100mV to 250Vac and input current spans from 10mA to 100mAac can be field

configured. For current input spans of 1 to 5 Amps a 0.1

M (5W) shunt resistor (Model# C006) is available.

The G168 is configurable as a single or dual setpoint alarm, with HI or LO trips and failsafe or non-failsafe

operation. Also included are adjustable deadbands (0.25 to 5% of full scale input) for each setpoint. The

G168 will accept any DC voltage between 9 and 30Vdc.

The G168 is equipped with three front panel LEDs. The first is a dual function LED labeled IN (input). This

green LED indicates the presence of DC power and input signal status. Active DC power is indicated by an

illuminated LED. If this LED is off, check DC power and wiring connection. If the input signal is more than

110% of the full scale range, the LED will flash at 8 Hz.

Two red TRIP LEDs indicate the re-lay state for each setpoint. An illuminated red LED indicates the tripped

condition.

The G168 is equipped with two SPDT (form C) relays, rated at 120Vac or 28Vdc at 5 amperes. Each of

these relays is independently controlled by the field configurable setpoint and deadband.

The field configurable G168 limit alarm setpoints can be configured for HI or LO, failsafe or non-failsafe

operation. Each of the setpoints have a respective HI or LO deadband. In a tripped condition, the setpoint

is exceeded and the appropriate red LED will illuminate. The trip will reset only when the process falls below

the HI deadband or rises above the LO deadband (see Figure 1). For proper deadband operation, the HI

setpoint must always be set above the LO setpoint.

In failsafe operation, the relay is energized when the process is below the HI setpoint or above the LO set-

point (opposite for non-failsafe). In the failsafe mode, a power failure results in an alarm state output.

LSI circuitry in the G168 prevents false trips by repeatedly sampling the input. The input must remain beyond

the setpoint for 100 milliseconds, uninterrupted, to qualify as a valid trip condition. Likewise, the input must

fall outside the deadband and remain there for 100 milliseconds to return the alarm to an untripped

condition. This effectively results in a "dynamic deadband" -based on time- in addition to the normal

deadband.

Input Range Selector

9 10

Current

Voltage

Table 1: G168 input range selector - switch settings

Key:

n ON

Load

Load

Diode

(optional)

Power

Power

MOV

0.1uF

Film

0.1uF

Film

Figure 3: AC Inductive Loads

Figure 2: DC Inductive Loads

47 ohm

1/2W

47 ohm

1/2W

Relay

Contacts

Relay

Contacts

+

-

Figure 1

Advertising