Description

Application

Diagnostic LEDs

The Ultra SlimPak G448 is a DIN rail mount, bridge or strain gauge input signal conditioner with 1800Vdc

isolation between input, output and power. The field configurable input and output offers flexible, wide

ranging capability for bridge or strain gauge input applications from 0.5mV/ V to over 50mV/V.

Wide ranging, precision zero and span pots allow 50% adjustablity of offset and gain within each of the 11

switch selectable input ranges. The output can be set for either 0-5V, 0-10V, 0-1mA, 0-20mA or 4-20mA.

This flexibility, combined with an adjustable (1 to 10Vdc) bridge ex-citation source, provides the user a

reliable, accurate instrument to isolate and condition virtually any bridge or strain gauge input.

The Ultra SlimPak G448 field configurable, bridge input signal conditioner is useful in isolating ground loops

and interfacing bridge sensors to data acquisition and control systems.

Three way isolation completely eliminates ground loops from any source. Isolation protects expensive

SCADA systems from ground faults and provides filtering for noise reduction which can be a significant

problem with small, millivolt, bridge signals.

Wide ranging flexibility allows the user to easily zero out dead-loads in weighing systems or configure bipolar

input ranges for expansion-compression or vacuum-pressure bridge applications.

High density DIN rail mounting offers an extremely compact solution for saving valuable panel space.

The G448 is equipped with a dual function LED signal monitor. The green, front mounted LED indicates both

DC power and input signal status. Active DC power is indicated by an illuminated LED. If the input signal is

more than 110% of the full-scale range, the LED will flash at 8Hz. If this continues to occur, you may wish to

change your full-scale input range setting.

Table 3:

Bridge excitation

selector-switch settings

Table 2:

Direct or reverse

operation setting

Table 1:

Input range selector-

switch settings

Table 4:

Output range

selector-swtich

settings