Technical data
Input
Input signal
0 ... 20 mA or 0 ... 10 V
Input voltage, max.
15 V (0 ... 10 V)
Input current, max.
25 mA (0 ... 20 mA)
Input resistance
50
Ω
(0 ... 20 mA)
500 k
Ω
(0 ... 10 V)
Output
Output signal
0 ... 20 mA or 4 ... 20 mA
or 0 ... 10 V
Load resistance
≤
500
Ω
(0 ... 20 mA, 4 ... 20 mA)
≥
1 k
Ω
(0 ... 10 V)
Accuracy at T
u
= 23 °C
± 0.2 % from end value
Temperature coefficient
≤
250 ppm/K from measured
value
Advertising