3.4 Pluggable cross-connections for voltage supply

(s. Fig. 4)

A maximum feed through of 2 A is possible.
If a signal conditioner is accidently rotated through 180°, the
cross-connection cannot be inserted.

3.5 Labelling possibilities

(s. Fig. 5)

WS 10 connector markers can be used to label module.

4

Calibration

Warning!!

The power supply must be disconnected, before
changing the signal conditioner settings using the
DIP switches.
Failure to observe will lead to considerable damage!

4.1 Equipment

Power supply 24 Vdc, 50 mA

Simulator for PT 100 or precision resistance decade

Current meter/voltmeter that can be so calibrated, as to allow
an accuracy of > 0.1 % from the upper range value