Page

3













1. Description and construction

The PRO-H Series power supplies are built-in units. The mounting position has to fulfil the requirements for fireproof case according to UL60950,

IEC/EN 60950 or other appropriate national standard. The relevant UL regulations or equivalent national regulations must be observed during

installation.
The PRO-H Series power supplies are designed for mounting on a DIN rail TS35 (DIN EN 50022-35x15/7.5) and for operation from 115 or

230VAC, 50/60Hz (Universal input voltage range for CP T SNT 70W 12V 6A, CP T SNT 90W 24V 3.8A and auto range for CP T SNT 140W

12V 12A, CP T SNT 180W 24V 7.5A, CP T SNT 180W 48V 4A, CP T SNT 360W 24V 15A, CP T SNT 360W 48V 7.5A, CP T SNT 600W 24V

25A and CP T SNT 600W 48V 12.5A single-phase systems.
The output voltage of the PRO-H Series power supplies is potential-free (floating), protected against short circuit and open circuit conditions (see

Fig 1.1, Fig 1.2 and Fig 1.3).

2. Installation

A sufficiently strong DIN-rail has to be provided. The correct mounting position for optimal cooling performance must be observed. Above and

below the power supply a minimum free space of 80mm [3.15in] is required and on each side of the power supply a minimum space of 50mm

[1.97in] is required which allows air convection. The air temperature measured 10mm [0.39in] below the power supply must not exceed the

specified values in the data sheet. Observe power derating above ambient temperatures of 40°C and at low line. (see Fig 4.1 and Fig 4.2)

2.1 Assembly

To fix unit on the DIN-rail, hook top part of clip on DIN-rail, push down- (see Fig 2.1) and inwards (see Fig 2.2) until you hear a clipping sound.
To remove the unit, pull the latch of the clip with the aid of an insulated flat head screwdriver (see Fig 2.3). When clip has cleared bottom DIN

rail remove the screwdriver from recess. Lift the unit off DIN-rail. See Fig 2.4.
Wall mounting or chassis mounting can be achieved by use of optional mounting brackets

CP MB01 (1 bracket, see Fig. 6.1) for CP T SNT

(70W 12V 6A, 90W 24V 3.8A, 140W 12V 12A, and 180W xx) or

CP MB02 (2 brackets, see Fig. 6.2 and Fig. 6.3) for CP T SNT (360W xx,

600W xx) . Remove the DIN-clips by removing the screw and place the mounting brackets in the same place as the DIN-clips.

Warning

The power supplies are constructed in accordance with the safety requirements of IEC/EN/UL 60950-1, CSA-C22.2 No.

60950-1-03, UL508, CSA-C22.2 No. 14-95, EN60204, EN50178, EN61558-2-4, CSA C22.2 No. 213 (Class I and II, Division

2) and ANSI/ISA 12.12.01. They fulfil the requirements for CE-compatibility and carry the CE-mark and are UL & cUL

approved by CSA and UL.
The PRO-H Series built-in power supplies were designed especially for use in process automation and other industrial applications.

Components with dangerously high voltage and high stored energy are located in the device. However, these are

inaccessible. Failure to properly maintain the power supply can result in death, severe personal injury or substantial property

damage.

The power supplies may o

nly be installed and put into operation by qualified personnel.

The

corresponding national regulations (e.g. UL, CSA, ANSI, VDE, DIN) must be observed. The successful and safe operation of

this power supply is dependent on proper storage, handling, installation and operation.
The potentiometer to adjust the output voltage is only allowed to be actuated using an insulated screwdriver, because

accidental contact may be made with parts inside the power supply carrying dangerous voltages.

Please observe following points before putting the device into operation:

• Read operating instructions thoroughly.
• That the mains connection has been carried out by a competent person and protection against electrical shock is

guaranteed!

• That the device can be disconnected outside the power supply in accordance with the regulations as in IEC/EN/UL/CSA

60950 or other national regulations.

• That the protective earth is connected.
• That the input wiring is sufficiently protected and dimensioned!
• That the output wiring is dimensioned according to the maximum output current or separately protected!
• Sufficient cooling is guaranteed!
• The temperature of the housing can become very high, depending on the ambient temperature and load.

Caution:

Risk of electrical shock and electrical discharge. The power supply must not be opened until at least 5 minutes after complete

disconnection of the mains.
Electrostatic sensitive device.

Qualified and trained personnel only may open the power supply.

Attention:

In case of non-observance or exceeding the mentioned limiting value of the data sheet, the function

and electrical safety can be impaired and can destroy the power supply.

Danger:

Never work on power supplies if power is applied!

Before installation ensure that the main switch is switched off and prevented from being

switched on again. In case of non-observance, touching of any live components or improper

dealing with this power supply can result in death or fatal injury.