WI-I/O-9-U2-TC - Thermocouple Adapter for WI-I/O-9-U2

Revision 1.6 - Oct 2011

Installation & Configuration Guide

Caution:

ESD Sensitive pins. Use ESD
handling precautions.

Thermocouple input terminals must
be within +/- 5V of the WI-I/O-9-U2
‘GND’ terminal

Connections

Installation

The WI-I/O-9-U2-TC adaptor board plugs into the
bottom 6 terminals on the WI-I/O-9-U2 terminal strip.
A separate 14 way terminal strip is provided to allow
connection to the remaining terminals.

Address locations

38005 = 32 bit Floating Point temperature value
38007 = 32 bit Floating Point Cold Junction value
30003 = Scaled 16 bit Analog value
30004 = Scaled 16 bit Cold Junction value

Analog Input Scale Examples

·

For normal Polarity setting Zero and Span to 0 and 100 respectively
will scale the register to read the temperature as an integer value,
e.g. 148.25 °C will read 14825 or 26.51 °C will read 2651

·

For normal Polarity, setting Zero and Span to 15019 and 682.6667
respectively will scale the register so that a temperature of -10 to
50°C will give a scaled range of 8192 to 49152

·

For Reverse Polarity, setting Zero and Span to 30948 and 455.106
respectively will scale the register so that a temperature of -50 to
40°C will give a scaled range of 8192 to 49152

Normal Type “T”

Thermocouple

*

Error Value is set in register 30003
when the thermocouple is open
circuit.

*

Error Value is set in register 30003
and 30004 when the thermocouple
adaptor is not fitted

Configuration

If ‘Thermocouple

Polarity’ selection is

reversed

Thermocouple wires

must be swapped,

e.g. (red) to TC+ &

(blue) to TC-

-Ve

+Ve

(+24V)

Thermocouple Adapter

COM

Constantan

(red)

Copper (blue)

N/C

N/C

TC+

TC-

Dip Switches

All Dip Switches

must be set to

the OFF position.

O

N

1

2

3

4

5

6

Type T

0°C to + 330°C

- 200°C to + 5°C

Type K

Type J

0°C to + 410°C

- 200°C to + 5°C

15°C to + 300°C - 210°C to + 10°C

Type

Normal

Reverse

Thermocouple Range @ Tamb (-40- +60)

Thermocouple Range @ Tamb (+10- +40)

Type T

- 25°C to + 365°C - 200°C to + 70°C

Type K

Type J

- 25°C to + 455°C - 200°C to + 70°C

- 10°C to + 345°C - 210°C to + 60°C

Type

Normal

Reverse

On the “I/O Configuration” web page select:

·

Select Thermocouple type from the drop down list. Options
are Type T, Type J, Type K.

·

Select the Polarity from the drop down list (Normal or
Reversed)

·

Set Thermocouple Error Value to a value the integer
registers (30003 and/or 30004) will go to during fail *

·

Press “Save and Activate Changes” button.

Inst_WI-I/O-9-U2 _TC_Adaptor_V1.6.vsd

PWR

RF

232

485

D

1

D

2

D

3

D

4

D

5

D

6

D

7

D

8

A

I 1

A

I2

A

I3
A

I4

A

O

1
A

O

2

G

N

D

+

2

4

V

+

-

+

G

N

D

+

2

4

V

A

I 1

-

A

I2

+

+

WI-I/O 9-U2

6720005011

Advertising
Table of contents