may be field converted for operation at elevations above

2000 ft (610 m) and/or for use with liquefied petroleum

fuel. See accessory kit installation instructions regarding

these accessories.
NOTE:

Furance gas input rate on rating plate is for

installation up to 2000 ft (610 m) above sea level. In U.S.A.
the input rating for altitudes above 2000 ft (610 m) must be
derated by 4% for each 1000 ft (305 m) above sea level. In
Canada the input rating must be derated by 10% for altitudes
of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.
For natural gas applications, gas pressure at unit gas

connection must not be less than 4 in. wg (996 Pa) or

greater than 13 in. wg (3240 Pa) while the unit is

operating. On 581J 04--06 high--heat units (see Table 2),

the gas pressure at unit gas connection must not be less

than 5 in. wg (1245 Pa) or greater than 13 in. wg (3240

Pa) while the unit is operating. For liquified petroleum

applications, the gas pressure must not be less than 11 in.

wg (2740 Pa) or greater than 13.6 in. wg (3390 Pa) at the

unit connection.
The gas supply pipe enters the unit at the burner access

panel on the front side of the unit, through the long slot at

the bottom of the access panel. The gas connection to the

unit is made to the

1

/

2

--in. FPT gas inlet port on the unit

gas valve

Table 2 – Natural Gas Supply Line Pressure Ranges

UNIT MODEL

UNIT SIZE

MIN

MAX

Low & Med Heat Units

581J*

04, 05, 06

4.0 in. wg

(996 Pa)

13.0 in. wg

(3240 Pa)

High Heat Units

58J*04*115

04

5.0 in. wg

(1245 Pa)

13.0 in. wg

(3240 Pa))

58J*05*150

05

58J*06*150

06

EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in damage

to equipment.
When connecting the gas line to the unit gas valve,

the installer MUST use a backup wrench to prevent

damage to the valve.

CAUTION

!

Install a gas supply line that runs to the unit heating

section. Refer to the NFPA 54/NFGC or equivalent code

for gas pipe sizing data. Do not use a pipe size smaller

than

1

/

2

--in. Size the gas supply line to allow for a

maximum pressure drop of 0.5--in wg (124 Pa) between

gas regulator source and unit gas valve connection when

unit is operating at high--fire flow rate.
The gas supply line can approach the unit in three ways:

horizontally from outside the unit (across the roof),

thru--curb/under unit basepan (accessory kit required) or

through unit basepan (factory--option or accessory kit

required). Consult accessory kit installation instructions

for details on these installation methods. Observe

clearance to gas line components per Fig. 13.

LEGEND

*

Field supplied.

NOTE: Follow all local codes.

NFGC – National Fuel Gas Code

STEEL PIPE

NOMINAL DIAMETER

(in.)

SPACING OF SUPPORTS

X DIMENSION

(ft)

1

/

2

3

/

4

or 1

1

1

/

4

or larger

6
8

10

X

BASE UNIT

BASE RAIL

ROOF
CURB

9” MINIMUM CLEARANCE
FOR PANEL REMOVAL

MANUAL GAS
SHUTOFF VALVE

*

GAS
REGULATOR

*

48” MINIMUM

DRIP LEG
PER NFGC

*

FIELD-FABRICATED
SUPPORT

*

FROM
GAS
METER

C11091

Fig. 13 -- Gas Piping Guide

(with Accessory Thru--the--Curb Service Connections)

Factory--Option Thru--Base Connections

(Gas Connections) —
This service connection kit consists of a

1

/

2

--in NPT gas

adapter fitting (brass), a

1

/

2

--in electrical bulkhead

connector and a

3

/

4

--in electrical bulkhead connector, all

factory--installed in the embossed (raised) section of the

unit basepan in the condenser section.

LOW VOLTAGE
CONDUIT
CONNECTOR

BRASS FITTING FOR 3 TO 6 TON UNITS.
STAINLESS STEEL FITTING FOR 7 1/2 TO 12 1/2 TON.

HIGH VOLTAGE
CONDUIT
CONNECTOR

C08015

Fig. 14 -- Fittings

The thru--base gas connector has male and female threads.

The male threads protrude above the basepan of the unit;

the female threads protrude below the basepan.
Check tightness of connector lock nuts before connecting

gas piping.
Install a

1

/

2

--in NPT street elbow on the thru--base gas

fitting. Attach a

1

/

2

--in pipe nipple with minimum length

of 16--in (406 mm) (field--supplied) to the street elbow

and extend it through the access panel at the gas support

bracket. See Fig. 15.