COVER REMOVED

SIDE VIEW

C07135

Fig. 44 -- Outdoor Air Quality Sensor Cover

Wiring the Outdoor Air CO

2

Sensor: A dedicated

power supply is required for this sensor. A two--wire cable

is required to wire the dedicated power supply for the

sensor. The two wires should be connected to the power

supply and terminals 1 and 2.

To connect the sensor to the control, identify the positive

(4 to 20 mA) and ground (SIG COM) terminals on the

OAQ sensor. See Fig. 42. Connect the 4 to 20 mA

terminal to RTU Open J4--5. Connect the SIG COM

terminal to RTU Open J4--6. See Fig. 45.

SEN

COM

J4-5

J4-6

OAQ Sensor/RH Sensor

24 VAC

C08463

Fig. 45 -- RTU Open / Outdoor CO

2

Sensor

(33ZCSENCO2) Connections

Smoke Detector/Fire Shutdown (FSD) —

On 581J units equipped with factory--installed Smoke

Detector(s), the smoke detector controller implements the

unit shutdown through its NC contact set connected to the

unit’s CTB input. The FSD function is initiated via the

smoke detector’s Alarm NO contact set. The RTU Open

controller communicates the smoke detector’s tripped

status to the BAS building control. See Figs. 34 and 35,

the RTU Open System Control wiring schematics.

The

Fire

Shutdown

Switch

configuration,

MENU

Config

Inputs

input

5,

identifies

the

normally open status of this input when there is no fire

alarm.

Space Humidity Sensor or Humidistat —
Perfect Humidity
t Control Wiring: In units equipped

with the Perfect Humidity option there are two pink

(PNK) wires loose in the control box used to control the

dehumidification function of the unit. These pink wires

are meant to be tied to a space humidistat or thermidistat

on an electromechanical unit. On RTU Open equipped

units these pink wires must be connected to J11--7 & 8 to

allow the Open board to operate the dehumidification

function for the unit. Disconnect the J11 Phoenix style

connector from the board and use the plug screws to

secure the pink wires in pins 7 and 8, reconnect the plug

to the board at J11.
Relative Humidity Sensors (Space or Duct Mounted):

The accessory space humidity sensor (33ZCSENSRH-01)

or duct humidity sensor (33ZCSENDRH-01) is used to

measure the relative humidity of air within the space or

return air duct. The RH reading is used to control the

Perfect Humidityt option of the rooftop unit. For wiring

distances up to 500 ft (152 m), use a 3--conductor, 18 or

20 AWG shielded cable. The shield must be removed

from the sensor end of the cable and grounded at the unit

end. The current loop power for sensor is provided by the

RTU Open controller as 24vdc. Refer to the instructions

supplied with the RH sensor for the electrical

requirements and terminal locations. RTU Open

configurations must be changed after adding an RH

sensor. See Fig. 46 and 47 for typical RH sensor wiring.

S

J4--1 or J4--4 = 24vdc loop power

S

J4--2 or J4--5 = 4--20mA signal input

NOTE: The factory default for dehumidification control

is normally open humidistat.

SW2

1

2

3

4

5

6

ON

Io

Vin

Gnd

Vo

MOUNTING
HOLES

WIRING
OPENING

Vin - J4-1 or J4-4 24Vdc
Io - J4-2 or J4-5 -20mA output

C11087

Fig. 46 -- Space Relative Humidity Sensor Typical Wiring

581J