SPECIFICATIONS — 558D036-072

UNIT SIZE

036

048

060

072

NOMINAL CAPACITY (tons)

3

4

5

6

OPERATING WEIGHT (lb)

Unit

Al/Al*

365

375

395

470

Economizer

Durablade

34

34

34

34

Parablade

42

42

42

42

Roof Curb†

115

115

115

115

COMPRESSOR

Hermetic

Quantity
No. Cylinders (per circuit)

1
2

1
2

1
2

1
2

Oil (oz)

50

50

50

54

REFRIGERANT TYPE

R-22

Operating Charge (lb-oz)

Circuit 1

3-6

4-11

5-13

7-10

Circuit 2

—

—

—

—

CONDENSER COIL

Enhanced Copper Tubes, Aluminum Lanced Fins

Rows...Fins/in.

1...17

1...17

1...17

2...17

Total Face Area (sq ft)

7.36

11.39

13.19

10.42

CONDENSER FAN

Propeller Type

Nominal Cfm

4100

4100

4100

4100

Quantity...Diameter (in.)

1...22.0

1...22.0

1...22.0

1...22.0

Motor Hp...Rpm

1

⁄

4

...1100

1

⁄

4

...1100

1

⁄

4

...1100

1

⁄

4

...1100

Watts Input (Total)

325

325

325

325

EVAPORATOR COIL

Enhanced Copper Tubes, Aluminum Double-Wavy Fins

Expansion Device

Acutrol™ Feed Device

Rows...Fins/in.

2...15

2...15

3...15

4...15

Total Face Area (sq ft)

4.17

5.5

5.5

5.5

EVAPORATOR FAN

Centrifugal Type

Quantity...Size (in.)

Std

1...10 x 10

1...10 x 10

1...11 x 10

1...10 x 10

Alt

1...10 x 10

1...10 x 10

1...10 x 10

—

Type Drive

Std

Direct

Direct

Direct

Belt

Alt

Belt

Belt

Belt

—

Nominal Cfm

1200

1600

2000

2400

Motor Hp

Std

—

—

—

—

Alt

—

—

—

—

Maximum Continuous Bhp

Std

.34

.75

1.20

2.40

Alt

1.00

1.00

1.80

—

Motor Frame Size

Std

48

48

48

56

Alt

48

48

48

—

Nominal Rpm High/Low

Std

860/800

1075/970

1075/970

—

Alt

—

—

—

—

Fan Rpm Range

Std

—

—

—

1070-1460

Alt

760-1000

835-1185

900-1300

—

Motor Bearing Type

Ball

Ball

Ball

Ball

Maximum Allowable Rpm

2100

2100

2100

2100

Motor Pulley Pitch Diameter A/B (in.)

Std

—

—

—

2.8/3.8

Alt

1.9/2.9

1.9/2.9

2.4/3.4

—

Nominal Motor Shaft Diameter (in.)

Std

1

⁄

2

1

⁄

2

1

⁄

2

5

⁄

8

Alt

1

⁄

2

1

⁄

2

1

⁄

2

—

Fan Pulley Pitch Diameter (in.)

Std

—

—

—

4.5

Alt

4.5

4.0

4.5

—

Belt, Quantity...Type...Length (in.)

Std

—

—

—

1...A...40

Alt

1...A...34

1...A...34

1...A...39

—

Pulley Center Line Distance (in.)

Std

—

—

—

14.7-15.5

Alt

10.0-12.4

10.0-12.4

14.7-15.5

—

Speed Change per Full Turn of

Std

—

—

—

80

Movable Pulley Flange (rpm)

Alt

48

70

80

—

Movable Pulley Maximum Full Turns

Std

—

—

—

5

From Closed Position

Alt

5

5

5

—

Factory Setting

Std

—

—

—

3

Alt

3

3

3

—

Factory Speed Setting (rpm)

Std

—

—

—

1225

Alt

856

975

1060

—

Fan Shaft Diameter at Pulley (in.)

1

⁄

2

1

⁄

2

1

⁄

2

1

⁄

2

HIGH-PRESSURE SWITCH (psig)**

Standard Compressor Internal Relief

450 ± 50

500 ± 50

Cutout

428

428

Reset (Auto.)

320

320

LOW-PRESSURE SWITCH (psig)**

Cutout

7 ± 3

Reset (Auto.)

22 ± 7

FREEZE PROTECTION THERMOSTAT (F)**

Opens

30 ± 5

Closes

45 ± 5

OUTDOOR-AIR INLET SCREENS

Cleanable

Quantity...Size (in.)

1...20 x 24 x 1

RETURN-AIR FILTERS

Throwaway

Quantity...Size (in.)

2...16 x 25 x 2

LEGEND

Al

— Aluminum

Bhp

— Brake Horsepower

FIOP — Factory-Installed Option
TXV

— Thermostatic Expansion Valve

*Evaporator coil fins/condenser coil fins.

†Weight of 14-in. roof curb.

**Requires the accessory controls upgrade kit.

††Circuit 1 consists of lower portion of both the condenser and evaporator coils, and

Circuit 2 consists of the upper portion of both coils.

࿣

The 559F300 units require 2-in. industrial-grade filters capable of handling face ve-
locities up to 625 ft/min (such as American Air Filter no. 5700 or equivalent).

NOTE: The 036-150 units have a loss-of-charge/low-pressure switch (accessory or op-
tion) located in the liquid line. The 180-300 units have a low-pressure switch (standard)
located on the suction side.