While the zones of A,B,C... are corresponding to different compressor running frequency.

ΔT=0℃ as default.

Note:

When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:

A~E: Increase the frequency to the higher level until to F10.

F: Keep the current frequency.

G: Decrease the frequency to the lower level until to F1.

H: Run at F1 for 1h.(if T1-Ts -ΔT >6℃, the compressor will stop)

Meanwhile, the compressor running frequency is limited by the current.

I3HEAT

I2HEAT

I1HEAT

Off

Decrease

Hold

Resume

Off: Compressor stops.

Decrease: Decrease the running frequency to the lower level.