Klimaire KSIN Series Service Manual User Manual
Page 66
Advertising

64
3.IPM continuity check
Turn off the power, let the large capacity electrolytic capacitors discharge completely, and dismount the IPM. Use a digital
tester to measure the resistance between P and UVWN; UVW and N.
Digital tester
Normal resistance
value
(+)Red
(-)Black
∞
(Several MΩ)
P
N
U
V
W
Digital tester
Normal resistance value
(+)Red
(-)Black
∞
(Several MΩ)
U
N
V
W
4. Indoor AC Fan Motor
Measure the resistance value of each winding by using the tester.
Position
Resistance Value
RPG13B
RPG13H
RPG20D
RPG15A
RPG25
RPG45C
Black - Red
530Ω±8%
(20℃)
575Ω±8%
(20℃)
400Ω±8%
(20℃)
75Ω±8%
(20℃)
287Ω±8%
(20℃)
172Ω±8%
(20℃)
White - Black
315Ω±8%
(20℃)
558Ω±8%
(20℃)
383Ω±8%
(20℃)
150Ω±8%
(20℃)
409Ω±8%
(20℃)
138Ω±8%
(20℃)
Advertising